How To Use A Megger On Cable

How to use a megger on cable
Press the test button on megger, the megger will generate current. This current flows through cable, the resistance in scale is noted which ranges between 35 to 100 Mega Ohms. Note to maintain this contact for 30 to 60 seconds. Acceptable IR for electrical cable = 1 Mega Ohm for 1000 V.
How do you use a Megger step by step?
How to Use a Megohmmeter
- Cut power. Make sure you eliminate any voltage running through the wires you want to test.
- Uninstall wires. Disconnect the wires you want to test from both ends of the circuit and all feeding wires in motors.
- Connect the ground lead.
- Connect to conductor. ...
- Build voltage. ...
- Read meter. ...
- Complete testing.
How do you test insulation resistance on a cable?
The Insulation Resistance test sequence:
- Connect one of the test leads of the Insulation Tester to the Line conductor and the other one to the Neutral conductor.
- Repeat the test process with one of the test leads on the Line conductor and the other one on the Earth conductor.
How do I know the Megger value of cable?
Test Voltage for Meggering: When AC Voltage is used, The Rule of Thumb is Test Voltage (A.C) = (2X Name Plate Voltage) +1000. When DC Voltage is used (Most used in All Megger), Test Voltage (D.C) = (2X Name Plate Voltage).
Why do you Megger a cable?
The purpose of Megger test equipment for cables is to measure the integrity of your insulation in megaohms, similar to an ohmmeter. The device itself consists of three essential components such as an alligator clip, an analog or digital meter, and a small button that generates a test current.
Why do we Megger the cable?
The Megger test is a method of testing making use of an insulation tester resistance meter that will help to verify the condition of electrical insulation. Insulation resistance quality of an electrical system degrades with time, environment condition i.e. temperature, humidity, moisture and dust particles.
What is a normal megger reading?
The rule may be stated: Insulation resistance should be approximately one megohm for each 1000 volts of operating voltage, with a minimum value of one megohm. For example, a motor rated at 2400 volts should have a minimum insulation resistance of 2.4 megohms.
How do you megger 3 phase?
Connect the megger leads between one stator terminal and motor body. Apply twice the motor operating voltage between one phase and the motor body. If Motor rated voltage is 440 volts, apply voltage 880 volts. We should test the older motor at less voltage( about 80% of the twice operating voltage).
What is a good number for a megger?
Anything reading between 2 megohms and 1000 megohms is usually considered a good reading, unless other problems have been noted. Anything less than 2 megohms indicates an insulation problem.
How do you test a XLPE cable?
ALL (XLPE and Paper Lead) cable shall be tested with a VLF alternating voltage whose waveform shall approximate a sinusoidal waveform of frequency 0.1 Hz. NOTE: VLF is the preferred method for testing ALL types of cables.
How do you test if a cable is damaged?
To test, connect the multimeter to each of the wire's ends. As before if a full circuit is made and there are no problems, when connected the multimeter should show a low reading. If the reading is showing 'I' it means, there is a break.
What is acceptable insulation resistance?
The rule states that insulation resistance should be approximately one megohm for each 1000 volts of operating voltage, with a one megohm minimum. (By following this rule, a motor rated at 2400 volts should have a minimum insulation resistance of 2.4 megohms).
How do you test a cable?
Tip to Tip Test
- Set the multimeter to resistance (ohms/Ω) and a select a small scale.
- Choose a flat wooden surface on which to perform the test. Position both of the cable's plugs on the table.
- Use the probes to touch the tips of the plugs. Place the red probe on one tip and the black probe on the other.
What is L and E in Megger?
Meggers is equipped with three connection Line Terminal (L), Earth Terminal (E) and Guard Terminal (G). Megger connections. Resistance is measured between the Line and Earth terminals, where current will travel through coil 1.
Can a Megger damage insulation?
Keep in mind that this test is non-destructive, so you don't have to worry about further damaging your motor's insulation. Your instrument will simply apply a voltage and measure the resulting current over the insulation's surface – giving you the resistance value. (Thanks Ohm's Law.)
Why do we check the insulation resistance of a cable?
Insulation resistance testing is a key test for electrical cables as it is a measure of how effectively the cable is insulated. Poor insulation may result in short circuit, electric shock or fire.
Why do you need insulation in cables?
Insulation materials resist electrical leakage, prevent the wire's current from coming into contact with other conductors, and preserves the material integrity of the wire by protecting against environmental threats such as water and heat. The safety and effectiveness of the wire depend on its insulation.
What is a good insulation reading?
Readings should be greater than 1MΩ for an Earthed system, or 2MΩ for Class 2 or “floating” systems. Ideally this reading should be as high as possible. PV150 can read up to 19.99MΩ, and the PV200/210 up to 199.99MΩ. A good result would be “>19.99MΩ” on the PV150, and “>199.99MΩ” on the PV200/210.
Can you Megger with a multimeter?
Megger is a high voltage equipment design to measure the insulation. A multimeter can not be used for this purpose.
What is a good megger reading for a 480V motor?
IEEE recommends that for motor starting that the operational voltage, expressed as a meg-ohm value doubled plus 1000 is the minimum meg value for starting. For a 480V motor that would mean . 480Meg x 2= . 960 Meg + 1000, so a minimum ground resistance for starting a 480V is 1.960 Meg or round up to 2 meg-ohms.